Product Details
Industrial chiller
Temperature control range: -40℃-0℃
Cooling capacity range: 10.4 KW-208 KW
Temperature control accuracy: ±1℃
Keywords:
Industrial chiller
Category:
Hotline:
Detailed Description
Main Features
1. Ultra-low temperature refrigeration: Using cryogenic refrigeration technology, the refrigerant temperature can reach -40℃, meeting the industrial needs of extreme low-temperature environments;
2. Precise temperature control: Equipped with a high-precision temperature control system, the temperature control accuracy can reach ±1℃;
3. Intelligent control: Microcomputer control system, using intelligent support for automatic adjustment, fault diagnosis and remote monitoring, simple operation, and high degree of intelligence;
4. Multifunctional protection: It has multiple safety protection functions such as overload protection, high and low pressure protection, and antifreeze protection to ensure the safe and reliable operation of the equipment.
5. Flexible adaptation: Different refrigeration capacities, cooling media, and operating temperature ranges can be customized according to customer needs to meet diverse application scenarios.
Core Application Industries
Chemical industry: Used in low-temperature reactions, gas liquefaction, condensation and recovery processes;
Food processing: Used in food quick-freezing, low-temperature refrigeration, freeze-drying, etc;
Electronics industry: Used in semiconductor manufacturing, laser cooling, precision instrument testing, etc;
Laboratory research: Used in low-temperature experiments, material testing, environmental simulation, etc;
Metal processing: Used in deep cold processing of metal materials.
Model |
MK-05AS-LT |
MK-08AS-LT |
MK-10AS-LT |
MK-15AD-LT |
MK-20AD-LT |
MK-25AD-LT |
MK-30AD-LT |
||
Parameters |
|||||||||
Rated refrigeration capacity KW |
Outlet temperature |
0℃ |
10.40 |
16.15 |
21.50 |
32.30 |
43.00 |
52.80 |
62.80 |
-5℃ |
8.64 |
13.35 |
17.90 |
26.70 |
35.80 |
43.80 |
51.80 |
||
-10℃ |
7.13 |
10.85 |
14.70 |
21.70 |
29.40 |
35.50 |
41.80 |
||
-15℃ |
5.83 |
8.50 |
11.85 |
17.00 |
23.70 |
27.70 |
32.60 |
||
-20℃ |
8.53 |
10.75 |
12.35 |
21.50 |
24.70 |
29.00 |
35.30 |
||
-25℃ |
7.18 |
9.03 |
10.35 |
18.06 |
20.30 |
24.05 |
29.40 |
||
-30℃ |
6.04 |
7.53 |
8.64 |
15.06 |
17.28 |
19.98 |
24.30 |
||
-35℃ |
5.09 |
6.24 |
7.16 |
12.48 |
14.32 |
16.74 |
20.40 |
||
Operating ambient temperature range |
-20℃-42℃ |
||||||||
Power supply |
3N-380V/50HZ |
||||||||
Rated total power |
KW |
4.74 |
7.19 |
8.69 |
13.80 |
17.47 |
21.40 |
26.46 |
|
Compressor |
Type |
Fully enclosed scroll compressor |
|||||||
Quantity |
1 |
1 |
1 |
2 |
2 |
2 |
2 |
||
Rated power KW |
3.75 |
6.00 |
7.50 |
6.0*2 |
7.5*2 |
9.4*2 |
11*2 |
||
Refrigerant |
Type |
R404A |
|||||||
Charging amount KG |
4.0 |
6.4 |
8.0 |
6.4*2 |
8.0*2 |
9.6*2 |
12*2 |
||
Throttling method |
External balance thermostatic expansion valve |
||||||||
Condenser |
Form |
High-efficiency copper tube corrugated aluminum fin |
|||||||
Fan |
Air volume M 3/h |
5000 |
8000 |
10000 |
15000 |
20000 |
25000 |
30000 |
|
Rated power KW |
0.44 |
0.44 |
0.44 |
0.7 |
0.97 |
1.10 |
1.46 |
||
Evaporator |
Type |
Stainless steel plate evaporator |
|||||||
Water volume M 3/h |
2.60 |
3.46 |
5.19 |
6.91 |
10.87 |
12.83 |
15.20 |
||
Water tank capacity L |
80 |
115 |
115 |
148 |
195 |
247 |
300 |
||
Inlet and outlet pipe diameter G |
G1" |
G1-1/2" |
G1-1/2" |
G2" |
G2" |
G2" |
G2-1/2" |
||
Circulation pump |
Rated power KW |
0.55 |
0.75 |
0.75 |
1.1 |
1.5 |
1.5 |
3.0 |
|
Rated head m |
25 |
31 |
27 |
28 |
34 |
29 |
34 |
||
Machine dimensions |
L/mm |
1200 |
1450 |
1560 |
1600 |
1800 |
2000 |
2400 |
|
W/mm |
600 |
720 |
720 |
800 |
900 |
1000 |
1000 |
||
H/mm |
1450 |
1550 |
1650 |
1900 |
1960 |
1980 |
1950 |
||
Unit weight |
KG |
220 |
300 |
345 |
410 |
590 |
650 |
740 |
|
Note:
1. Table refrigeration capacity calibration conditions: The temperature difference between the inlet and outlet of the refrigerant is 5℃, and the ambient temperature is 30℃;
2. Neutral ethylene glycol antifreeze must be used as the circulating medium, and the freezing point of ethylene glycol must be 10℃ lower than the actual control temperature;
3. Air-cooled units must be installed in a well-ventilated place (such as outdoors, on the roof), and ensure that the air duct system is unobstructed;
4. Specifications and performance may change due to product improvements without further notice.
Previous Page
Next Page
Next Page
Next Page
Related Products
Temperature control range: 5℃-25℃
Cooling capacity range: 2.94 KW-181.68 KW
Temperature control accuracy: ±1℃
Water-cooled industrial chiller
Temperature control range: 5℃-25℃
Cooling capacity range: 9.59 KW-198.12 KW
Temperature control accuracy: ±1℃
Temperature control range: 5℃-25℃
Cooling capacity range: 110 KW-1500 KW
Temperature control accuracy: ±1℃
Temperature control range: 5℃-25℃
Cooling capacity range: 110 KW-1530 KW
Temperature control accuracy: ±1℃
Online Consultation